Smoke extract
Maintaining a smoke-free area creates a means of escape and better access for fire fighters.
10 Storey building
For space-constrained multi-storey residences requiring mechanical smoke extraction to maintain smoke-free means of escape and fire fighter access. Mechanical smoke extract from corridors/lobbies provide reduced riser areas, can provide increased travel distances and is less susceptible to adverse wind pressures acting on the discharge Air Operating Vent [AOV] when compared to natural smoke vent systems.
Solution
1No. SMHA extract fan was selected to provide the required extract duty, 20No. ESAS smoke control dampers – one per level on extract side and 1 per level on make-up air route were provided to allow for only the fire level to have smoke ventilation, all other levels were closed off to prevent the spread of smoke. CFD analysis was also provided for this project to demonstrate the visibility achieved.
EXAMPLE BUILDING
10 storey apartment building with a calculated fire load of 1MW in a residence with door held ajar by debris during occupant escape, causing smoke spread into the connecting lobby with other residences and an extended travel distance to the single escape stair core.
Ventilation requirement: smoke extract from corridor to increase visibility for fire-fighter access.
2 Storey building
For Multi-compartment buildings needing fire-rated ducts and dampers to maintain compartmentation between areas.
Fast-Response dampers are required to limit smoke spread between compartments. CE marking ensures a guaranteed level of quality and air leakage for life-safety equipment.
Products included in this solution
-
HT JMv® AEROFOIL AXIAL FLOW FAN
- Innovative, CFD optimized design - improved aerodynamic efficiency.
- Certified in accordance with EN12101-3, for Smoke Extraction up to 400°C for 2 hours.
- Fully cased design – quick, simple and cost effective installation.
-
ESAS SMOKE CONTROL DAMPER
- CE marked
- Easy and cost effective installation
- Manual and automatic activation